James Hirsch & Associates is currently
implementing new chiller algorithms in DOE-2, and defaults performance
curves for screw chillers will be included.
For both reciprocating and
screw chillers, the program will use different performance curves depending on
the number of compressors in the machine. The program will also model
centrifugal chillers with variable-speed drives. Since some of these
curves utilize new types of CURVE-FITS, they require a new version of
DOE-2.2 which won't be released for another month or two.
In the meantime, for current versions of DOE-2.2,
the following models a water-cooled screw:
"ScrewH2O-Cap-fCHWT&LCT" = CURVE-FIT TYPE =
BI-QUADRATIC-T INPUT-TYPE =
DATA IN-TEMP1 = ( 44.0, 44.0, 44.0,
44.0, 44.0, $ CHW
T
48.0, 48.0, 48.0, 48.0, 48.0,
52.0, 52.0, 52.0, 52.0, 51.0,
40.0, 40.0, 40.0, 40.0, 40.0) IN-TEMP2 = ( 85.0, 75.0, 70.0,
95.0, 100., $
ECT
85.0, 75.0, 70.0, 95.0, 100.,
85.0, 75.0, 70.0, 95.0, 100.,
85.0, 75.0, 70.0, 95.0, 100.) OUTPUT = ( 1.00, 1.07, 1.10, 0.92, 0.89, $ Capacity
ratio
1.09, 1.16, 1.18, 1.00, 0.96,
1.18, 1.24, 1.26, 1.09, 1.05,
0.92, 0.99, 1.02, 0.85, 0.83)
.. "ScrewH2O-EIR-fCHWT&LCT" = CURVE-FIT
TYPE =
BI-QUADRATIC-T INPUT-TYPE =
DATA IN-TEMP1 = ( 44.0, 44.0, 44.0,
44.0, 44.0, $ CHW
T
48.0, 48.0, 48.0, 48.0, 48.0,
52.0, 52.0, 52.0, 52.0, 51.0,
40.0, 40.0, 40.0, 40.0, 40.0) IN-TEMP2 = ( 85.0, 75.0, 70.0,
95.0, 100., $
ECT
85.0, 75.0, 70.0, 95.0, 100.,
85.0, 75.0, 70.0, 95.0, 100.,
85.0,
75.0, 70.0, 95.0, 100.) OUTPUT = ( 1.00, 0.85, 0.78, 1.20, 1.31, $ EIR ratio
0.94, 0.81, 0.74, 1.13, 1.24,
0.90, 0.77, 0.71, 1.07, 1.17, 1.06, 0.89, 0.82, 1.27, 1.39) ..
$ Two circuits, one compressor/circuit "ScrewH2O-EIR-fPLR&dT-1Comp/Ckt" = CURVE-FIT
TYPE =
QUADRATIC INPUT-TYPE =
DATA INPUT = ( 1.00, 0.75, 0.50, 0.25,
0.10) OUTPUT = ( 1.00, .906, .538, .332, .141) .. $ Two circuits, two compressors/circuit "ScrewH2O-EIR-fPLR&dT-2Comp/Ckt" =
CURVE-FIT
TYPE = QUADRATIC
INPUT-TYPE =
DATA INPUT = ( 1.00, 0.75, 0.50, 0.25,
0.10) OUTPUT = ( 1.00, .842, .664, .289, .151) ..
"A Generic Screw Chiller" = CHILLER TYPE = ELEC-HERM-REC ELEC-INPUT-RATIO = .202 CAPACITY-FT = "ScrewH2O-Cap-fCHWT&LCT" EIR-FT = "ScrewH2O-EIR-fCHWT&LCT" EIR-FPLR = "ScrewH2O-EIR-fPLR&dT-1Comp/Ckt" etc. ..
Hope this helps! |
BEGIN:VCARD VERSION:2.1 N:Gates;Steven;D. FN:Steven D. Gates TEL;WORK;VOICE:(916) 962-7402 TEL;HOME;VOICE:(916) 638-1203 TEL;WORK;FAX:(916) 962-0101 TEL;HOME;FAX:(916) 638-1203 ADR;WORK:;;11608 Sandy Bar Ct.;Gold River;CA;95670-7645 LABEL;WORK;ENCODING=QUOTED-PRINTABLE:11608 Sandy Bar Ct.=0D=0AGold River, CA 95670-7645 EMAIL;PREF;INTERNET:Steve.Gates@xxxxxxxx REV:20020116T203113Z END:VCARD =====================================================You received this e-mail because you are subscribed to the BLDG-SIM@xxxxxxxx mailing list. To unsubscribe from this mailing list send a blank message to BLDG-SIM-UNSUBSCRIBE@xxxxxxxx