[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

[BLDG-SIM] eQuest Detailed Edit mode level question..



John,

As far as I know there isn't a zone level temperature reset schedule.

The only way to do that is to create a custom time schedule that changes
your zone thermostat setting based on the TMY2 weather file you're
simulating.

If you look back in the Bldg-Sim archives I posted a template for an
8,760 hourly input schedule that you can paste into your input file.
It's pretty easy to pre process your data in Excel or a database and use
macros to prepare all the schedule code for the input file.

MMT


Michael Tillou, PE
ETC Group, Inc - Energy Engineering for a Sustainable Future
Ph:413-458-9870


-----Original Message-----
From: BLDG-SIM@xxxxxxxx [mailto:BLDG-SIM@xxxxxxxx] On Behalf Of Aulbach,
John
Sent: Thursday, January 04, 2007 5:21 PM
To: BLDG-SIM@xxxxxxxx
Subject: [BLDG-SIM] eQuest Detailed Edit mode level question..


 
Hi Gang:

Happy New Year.

I am at the Detailed Edit mode of eQuest(theoretical Point of No
Return). I wish to incorporate a zone thermostat reset schedule based on
Outdoor Air Temperature, NOT TIME.

Any suggestions as to how to do it?

John R. Aulbach, PE, CEM
Project Manager
Nexant, Inc.
100 North Barranca, Suite 820
West Covina, CA 91791 USA
Phone: 626-430-9054
Fax: 626-430-9060
email: jaulbach@xxxxxxxxxx
 

==================
You received this e-mail because you are subscribed 
to the BLDG-SIM@xxxxxxxx mailing list.  To unsubscribe 
from this mailing list send a blank message to 
BLDG-SIM-UNSUBSCRIBE@xxxxxxxx


=====================================================You received this e-mail because you are subscribed
to the BLDG-SIM@xxxxxxxx mailing list.  To unsubscribe
from this mailing list send a blank message to
BLDG-SIM-UNSUBSCRIBE@xxxxxxxx